In my previous post, I have discussed about the instruction of wiring. Now, suppose you have made the wiring complete
and going to power it up. Stop one second, are all the connections tested?
Before giving the power some tests must be done.
1.
Insulation resistance test
This test is
done to know whether there is any leakage in the conductors. There are mainly
two types of leakage.
(a)between
phase and neutral, (b)between conductors and earth.
For the first
part of the test, the main switch should be opened and all electrical
appliances removed from the circuit. All controlling switches should be closed.
The resistance between phase and the neutral conductors is measured with a 500
volt megger.
Resistance of each circuit should not be3 less than 10MegaOhm.
For second
part of the testing between conductor and earth, all controlling switches
should be closed, all lamps put in position, all fuses provided and phase and
neutral conductors short circuited at the main switch. The insulation
resistance between conductors and earth is then measured. This value should not
be less than 5ohm.
2.
Continuity Test
In this test,
all the fuses and links are provided and switches closed. All outlets are
shorted one by one and continuity checked. The resistance between phase and
neutral is measured with a 500v megger at the main switch. the value shouls be
nearly zero.
3.
Polarity test
4.
This test is done to ensure that
switches are controlling the phase wires and not the neutral wires. One
terminal of the megger is connected to the phase and main switch and the other
to the terminal of the control switch. the megger in this condition should read
zero, otherwise it indicates that the switches are controlling the neutral
wire.
5.
Earth Resistance Test
For this, one
terminal of earth tester is connected with the earth to be tested and two other
terminals with two earthing electrodes
placed at distances of 22.5m and 45m respectively. the tester is run with
constant speed for about a minute. The value of resistance should not be more
than 2ohms for good condition.
Hope you have
enjoyed the post . thank you for coming to my blog.
For any
enquiry you can contact with me
Whats app-
9641977195 (india)